Monitored interconnections, flow boundaries and outages¶
The file KOMBSNITT.DAT contains input for:
Interconnections with power flow monitoring
Maximum flow limit
Outages
End-of-file
The file format follows:
First line: Total number of monitored interconnections
Then, for each of the monitored interconnections:
Line 1: Name From, Name To,
Line 2: No. of lines in intercon. (NL), Cap. From-To, Cap. To-From, No. of revisions (NR),
Line 3: (3+NR):
From Week, To Week, Capacity out From, Capacity out To,
Line (4+NR): (4+NR+NL):
Busbar From, Busbar To, Share From, Share To, Describing text,
1,1, # Dummy: not relevant for Samnett, but must be included
1,1,
Note |
|---|
|
A connection between the same two nodes should only be registered once. Samnett will automatically discover and add parallel lines. |
It is important that the N interconnections in EFI-SNITT.DAT are identical and in the same order as the N first transport channels in MASKENETT.DATA and |
- Capacity outage modelled in |
Simple example file¶
3, # Interconnections
'numedal','tev', # Interconnection: name from, name to
1, 200.000000, 200.000000,0, # Interconnections: Number of lines, capacity from [MW], capacity_to [MW], number of outages
10007,20008, 1.000000, 1.000000, # Line: Busbar from, busbar to, share from, share to
1, 1, # Dummy: not relevant for Samnett, but must be included
1, 1,
'tev','otra', # Interconnection: name from, name to
2, 200.000000, 200.000000,0, # Interconnections: Number of lines, capacity from [MW], capacity_to [MW], number of outages
20022,30013, 1.000000, 1.000000, # Line: Busbar from, busbar to, share from, share to
20022,30014, 1.000000, 1.000000,
1, 1, # Dummy: not relevant for Samnett, but must be included
1, 1,
'numedal','otra', # Interconnection: name from, name to
1, 200.000000, 200.000000,0, # Interconnections: Number of lines, capacity from [MW], capacity_to [MW], number of outages
10021,30023, 1.000000, 1.000000, # Line: Busbar from, busbar to, share from, share to
1, 1, # Dummy: not relevant for Samnett, but must be included
1, 1,
-1, # End of file
Outages (revisions)¶
In the following we described how to model revisions in KOMBSNITT.DAT through an example.
'FINNMARK','TROMS',
3,800,270,2, # Revisions
1,10,-600,-400, # from week; to week; capacity reduction in pos. direction [MW]; capacity reduction in neg. direction [MW]
21,22,-400,-400, # from week; to week; capacity reduction in pos. direction [MW]; capacity reduction in neg. direction [MW]
58521,58051,1.0,1.0,
58503,58053,1.0,1.0,
58513,58483,1.0,1.0,
On the second line and fourth column we define the number of outages to be read (2). On the third and fourth lines these outages are defined on the following format:
from week; to week; capacity reduction in pos. direction [MW]; capacity reduction in neg. direction [MW]
The first capacity outage between areas FINNMARK and TROMS last from week 1 to 10 and reduces capacity in the direction towards TROMS by 600 MW and towards FINNMARK by 400 MW. Capacity reduction can be defined as positive or negative numbers, both are treated as reductions.
End-of-file¶
The end-of-file marker is -1. When the marker is found file parsing ends.